Announce active alarms by voice on the operator client.

How-to GuidesSolution ExamplesFeature ExamplesIndustrial Operations Examples → Alarm Voice Announcement Example



Import the VoiceAlarm plugin from Solution → Import Plugin.

Download, unzip and move it to "C:\Users\Public\Documents\FrameworX\Exchange": VoiceAlarm.zip (10.1.5e or later)

The plugin contains a single Script Class. It requires no tags, no device configuration and no database.




Summary

This feature speaks alarm messages aloud on the operator client, so an operator who is not looking at the screen still learns that something needs attention and how serious it is.

It announces the highest-priority active alarm, read from @Alarm.PriorityItem. It works on both client types from the same code:

  • Windows client (Rich Client / Smart Client) — speaks through System.Speech.Synthesis, using the voices installed in Windows.

  • HTML5 / browser client — speaks through the browser's built-in Web Speech API. Nothing to install and nothing to host.

Speech happens on the client, never on the server. A server running as a Windows Service has no audio device, and a request to speak there returns successfully and makes no sound.

Step 1 — Import the plugin

In the Designer, go to Solution → Import Plugin and select the VoiceAlarm plugin. This adds one Script Class named VoiceAlarm, with its Domain set to Client.

The Client domain matters: it gives every connected station its own instance, so each operator station decides independently what to announce.

Step 2 — Call it from a display that is always open

The class does nothing on its own. It must be called repeatedly from the code-behind of a display that stays open for the whole session.

The Header is the recommended place, because it is part of the startup layout and is open on every screen. Any always-open display works — a footer or a permanently docked panel is equally valid.

Open the display, go to the CodeBehind tab, and add:

public void DisplayIsOpen()
{
    @Script.Class.VoiceAlarm.CheckAlarmToVoice();
}

Then set the display's DisplayIsOpen Cycle property to 250 (milliseconds). That is how often the check runs.

That is the whole installation. There is nothing else to configure to get spoken alarms.

How it behaves when several alarms are active

This is the part worth understanding, because the behaviour is deliberate and it is not what a naive implementation would do.

It always speaks the most important alarm first

The class never maintains its own list of alarms to read out. On every check it asks the platform a single question: what is the highest-priority active alarm right now?

While a phrase is playing, the check does nothing at all. When the phrase finishes, it asks the question again — and announces whatever is the top alarm at that moment.

Why it does not queue

Queueing announcements sounds harmless and behaves badly. Alarms in a cascade usually arrive least-important first, so a queue reads them in exactly the wrong order, and keeps reading long after the situation has changed.

With five alarms arriving inside 1.2 seconds, a queue produces this:

Time

Queued announcement

0–3 s

Motor D overload (priority 2 — the least important)

3–6 s

Valve B fault (priority 4)

6–9 s

High level on tank C (priority 6)

9–12 s

High discharge pressure on compressor E (priority 8)

12–15 s

High temperature on pump A (priority 9 — the most serious, announced last)

Fifteen seconds of narration for an event that lasted just over one, and the alarm that mattered most is spoken twelve seconds late.

The same burst with this feature:

Time

Announcement

0–3 s

Motor D overload (the top alarm at that instant)

0.3–1.2 s

four more alarms arrive — nothing is queued

3.25–6.25 s

High temperature on pump A (now the top alarm)

The alarms it did not name are not forgotten

They stay active, and each is announced when it becomes the highest-priority alarm — typically once the more serious alarm above it has been acknowledged or has cleared.

So that silence is never mistaken for an all-clear, each announcement ends with a count of the others:

"Attention. High temperature on pump A."
   … short pause …
"Thirty-nine more alarms active."

The count is spoken as a separate sentence after a configurable pause (OthersDelay), so it registers as its own piece of information rather than running on from the alarm text. Set AnnounceOthers to false to turn it off.

During a large alarm flood, the useful message is "this is the worst thing, and there are many". The alarm list on screen carries the full inventory; the voice channel carries urgency and priority.


Configuration

Every setting has a working default — the feature runs with no configuration at all. Set properties from the code-behind before calling CheckAlarmToVoice(), or from a startup script on the client.

Property

Default

Purpose

Enabled

true

Master on / off for this station.

MinPriority

0

Ignore alarms below this priority. 0 announces every priority.

OnlyGroups

(empty)

Comma-separated alarm group names to announce. Empty means all groups.

SpeakOnlyOnce

true

Announce each alarm occurrence once. An alarm that clears and re-triggers is a new occurrence and is announced again.

Template

Attention. {Message}.

The spoken sentence. Placeholders: {Message}, {TagName}, {Group}, {Priority}.

Volume

100

0 to 100.

Rate

0

Speaking rate, -10 (slowest) to 10 (fastest).

Language

en-US

Voice language. Must match a voice available on the client.

AnnounceOthers

true

Append the count of other active alarms.

OthersDelay

1500

Milliseconds of silence between the alarm and the count sentence.

Example — announce only critical alarms, in a calmer voice:

public void DisplayOpening()
{
    @Script.Class.VoiceAlarm.MinPriority = 8;
    @Script.Class.VoiceAlarm.OnlyGroups  = "Critical";
    @Script.Class.VoiceAlarm.Rate        = -2;
}

Because the class runs in the Client domain, these settings apply to that station only. A control-room station and a maintenance laptop can have different thresholds.

Testing

Call TestSpeak from a button to confirm audio is working without waiting for a real alarm:

@Script.Class.VoiceAlarm.TestSpeak("Voice alert test.");


Alternative: speaking from the server with an alarm notification method

There is a second way to turn an alarm into speech, and it predates this plugin: give an AlarmGroup a NotificationMethod and let the alarm engine call your code on every alarm event. It has fewer moving parts than a client plugin, and for some plants it is the better fit.

Create a Script Class with a method whose signature matches the alarm callback exactly, then set the group's NotificationMethod to <ClassName>.<MethodName>. The NotificationMethod column is hidden by default in Alarms → Groups — right-click the column headers to enable it. You can also give each alarm a spoken wording of its own by editing the Message column in Alarms → Items.

//Pay attention to the function's parameter.
//It has to be like this to correctly connect with the AlarmGroup.
public void AlarmCustom(AlarmEventInfo[] items)
{
	if (items[0].State == 1)
	{
	    SpeechSynthesizer synth = new SpeechSynthesizer();
	
	    // Configure the audio output. 
	    synth.SetOutputToDefaultAudioDevice();
	
	    // Speak the message associated with the AlarmItem.
	    synth.Speak(items[0].Message);
    }
}


The difference that decides which one to use: an alarm notification method is a server-side callback, so SetOutputToDefaultAudioDevice resolves to the audio device of the machine running the Runtime. The speech comes out of the server. That is what you want when the server sits in the control room behind one set of speakers. It is not what you want when operators are at their own stations, or on a browser client, because those machines never hear it.

This plugin takes the other route. Its Script Class runs in the Client domain and is driven from a display, so every announcement is produced on the operator's own station, browser clients included.


Alarm notification method

VoiceAlarm plugin (this page)

Where the audio plays

The Runtime server machine

Each operator client, browser clients included

What triggers it

An alarm event callback from the AlarmGroup

A display poll reading @Alarm.PriorityItem

During an alarm flood

Fires for every alarm event, in the order they arrive

Highest priority first, then a count of the rest

Browser client

No

Yes

Setup

One Script Class plus the group's NotificationMethod

Import the plugin, add one line to a display


Two things to watch in the server-side sample above if you adopt it as written. Speak is synchronous, so it holds the alarm notification thread for the whole phrase — use SpeakAsync if alarms can arrive faster than they can be read aloud. And the SpeechSynthesizer is created per event and never disposed; keep one instance for the class instead of allocating a new one on each call.

This page supersedes Script for TextToSpeech Example, which documented the server-side notification-method approach on its own. That page carries a downloadable solution demonstrating it.


Requirements and limitations

  • No tags are required. The class reads @Alarm.PriorityItem and @Alarm.TotalCount, which are platform objects. It creates nothing in the Unified Namespace.

  • The client needs an audio device. Announcements are produced on the operator station, not the server.

  • Browser clients need one user interaction first. Browsers block audio until the user has clicked somewhere on the page — logging on normally satisfies this. Until then the browser stays silent.

  • Voices come from the client machine. On Windows they are the installed SAPI voices; in a browser they come from the browser and operating system. If no voice matches Language, a default voice is used instead and the substitution is recorded in the trace log.

  • One speaking station per area. Every client with the feature enabled announces independently. Two stations within earshot will talk over each other, so enable the voice on one station per room and leave it off elsewhere.

  • Announcements are paced by speech, not by alarms. A phrase takes two to three seconds, so in a fast cascade only the alarms that reach the top of the priority list are named individually. This is intended — see the section above.

A single upset raising dozens of alarms is a sign that alarm rationalisation is incomplete. Standards such as ISA-18.2 and EEMUA 191 address this upstream, with techniques like state-based suppression and first-out logic, so that one designed alarm replaces the cascade of consequences. Voice announcement is a safety net for the operator, not a substitute for that work.