How the OPC UA Client connector maps to the OPC UA specification: which features it exposes, under which name, and which values are fixed.
Connectors Library → Browse By Connector Group → Standard Protocols → OPC UA Client Connector → OPC UA Client Specification Mapping
Overview
This page lists the OPC UA specification items (OPC 10000 series, cited by Part) that matter to a client, and shows how the FrameworX OPC UA Client connector handles each one. It describes the released FrameworX 10.1.6 (Update 6a), OPC UA Client driver version 1.1.0.1. Sentences that start with "In the next FrameworX update" describe changes planned for the next update; until it is installed, the connector behaves as the rest of the row describes. Setting names are the ones shown on the Station and Point configuration.
Status values:
- Configurable: you set it in the connector.
- Fixed: the connector uses its own value, with no setting.
- Fixed (automatic): the connector reads the value from the server.
- Library default: the connector does not set it; the default of the embedded OPC UA library applies.
- Next update: not available in 10.1.6; planned for the next FrameworX update.
Specification items
Transport and discovery
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
| Station > URL | Configurable | Free text | Only |
GetEndpoints (Part 4) | Station > Discovery button | Configurable | Without a port, tries 4840, 49320, 62841, 4845 and 49380 | Designer only. Lists URL, security mode and security policy of the endpoints the server returns. In the next FrameworX update, only |
FindServers (Part 4) | Station > Discovery button | Next update | - | In 10.1.6, Discovery uses GetEndpoints only. In the next FrameworX update, Discovery also asks each server it reaches for the servers it knows and lists their |
Endpoint selection (Part 4) | Discovery, row selection | Fixed | URL and a security flag | Only the URL is stored. Disable Security is set when the selected row uses mode None. The row's policy and mode are not stored. |
EndpointUrl and DiscoveryUrl (Part 4) | Host Override | Configurable | Empty | Host Override replaces the host or port before connecting. |
Security
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
Application instance certificate (Parts 4 and 6) | Station > Certificate (Default / Custom); key and hash in the Designer certificate generator | Configurable | Key 1024 (default), 2048 or 4096 bits; SHA-1 (default) or SHA-256 | The key size and the hash are chosen in the Designer certificate generator, not on the Station. With security on and no certificate, the client does not connect and keeps retrying, without a message that names the certificate. In the next FrameworX update, the Devices trace and the station status name the missing certificate, where it is expected and how to create it with the Certificate button of the Station. A server that offers only Basic256Sha256 needs a key of 2048 bits or more and SHA-256. |
Trust list (Parts 2 and 4) | Certificate Default or Custom; trusted, issuers and rejected folders | Configurable | Default | Default trusts an unknown server certificate on the first connection and stores it. Custom accepts only the certificates in the trusted folder. |
SecurityPolicy (Part 7) | Disable Security | Fixed | None, or the best policy the server offers | The policy itself is not selectable. |
Automatic policy selection | None | Library default | The most secure policy the server offers that the client certificate supports | Use a 2048-bit SHA-256 certificate to reach Basic256Sha256 and newer policies. When the server advertises its endpoints on a port other than the one the Station uses (Host Override, NAT or port mapping), the connector takes the first endpoint the server lists. |
MessageSecurityMode (Part 4) | None | Fixed | None, or the best mode the server offers | Sign or SignAndEncrypt cannot be forced. |
Anonymous user token (Part 4) | User Name left empty | Configurable | Default | |
UserName user token (Part 4) | User Name and Password | Configurable | Empty |
Session
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
Session timeout (Part 4) | None | Library default | 10 min (600000 ms) | The server can revise the value. |
Reconnection | None | Fixed | 2, 4, 8, 16 and then 30 s (from 10.1.6) | Reconnection is handled by the connector itself. |
Session keep-alive (Part 4) | None | Library default | Status read every 5 s | Each session reads the server's CurrentTime, State, SecondsTillShutdown and ShutdownReason every 5 s. |
Sessions per Node | Use Single OPC Connection | Configurable | On | On: one session for writes and status and another one for the items. Off: one more session and one more subscription per read group. |
Addressing
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
NodeId | Point > Address | Configurable | - | |
NodeId in namespace 0, | Point > Address | Configurable | - | In subscription mode these points stay Uncertain; read them with Enable Read Polling. In the next FrameworX update, they also update in subscription mode. |
NodeId | Point > Address | Next update | - | In 10.1.6, the GUID text is sent as a string identifier and the server does not find the node, so a point with a |
ExpandedNodeId | Point > Address | Next update | - | Not supported in 10.1.6. In the next FrameworX update, a point addressed with |
ExpandedNodeId | Point > Address | Next update | - | Not supported in 10.1.6. In the next FrameworX update, |
NamespaceArray, index and URI (Part 5) | Address text | Fixed | Numeric index | With |
MaxNodesPerBrowse (Part 5) | None | Fixed (automatic) | Read from the server | It does not change how the connector browses. |
Arrays | Point > Modifiers > Array; tag | Configurable | Modifier size | The point on element 0 receives the array and fills the tag elements. A write rewrites the whole array. |
Structure members | Point on a UserType tag; Import address | Configurable | - | Uses the member node, or the decoded field of the parent structure. Writing one member rewrites the whole structure. Structures received by subscription show Good quality and the time of reception, not the quality and timestamp sent by the server. In the next FrameworX update, the Station option Structure Server Status (off by default) makes them take the quality and the source timestamp sent by the server. |
Read and write
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
Read (Part 4) | Enable Read Polling; AccessType | Configurable | Off | Reads at the AccessType rate. |
maxAge (Part 4) | Read From Device | Configurable | Off; on sends maxAge 0 | The setting applies to single reads only. Polled reads always send maxAge 0, so they always read from the device. In the next FrameworX update, Read From Device is on by default and polled reads follow it too: on reads from the device, off lets the server answer from its cache. A node saved in 10.1.6 keeps reading from the device. |
TimestampsToReturn (Part 4) | None | Fixed | Source for subscriptions; Both for polling and single reads | Session status reads use Neither. |
SourceTimestamp and ServerTimestamp (Part 4) | Use Computer Timestamp | Configurable | Off | Off: scalars and arrays use the SourceTimestamp; structures received by subscription use the time of reception. On: the local time of reception. |
StatusCode to quality (Part 4) | Tag quality | Fixed | Bad, Uncertain, Good | Only the severity is kept; sub-codes are not. |
Write (Part 4) | AccessType (WriteEvent, WriteTrigger) | Configurable | - | One node per call, without status or timestamp. One retry on failure. |
Server operation limits (OperationLimits)
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
MaxNodesPerRead (Part 5) | None | Fixed (automatic) | Read from the server; read groups of 75% of the limit | In polling mode, keep ReadGroupMaxSize at or below 75% of the server's MaxNodesPerRead. In the next FrameworX update, every point receives its own value, whatever the read group size. |
MaxMonitoredItemsPerCall (Part 5) | None | Fixed (automatic) | Read from the server; 100 when the server does not publish it | Batch size when monitored items are created. |
Subscriptions and monitored items
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
Subscription or periodic read | Enable Read Polling | Configurable | Off (subscription) | |
PublishingInterval (Part 4) | Refresh Rate | Configurable | 500 ms | Data does not arrive faster with a Refresh Rate below 250 ms, because the sampling interval is fixed at 250 ms. |
Revised PublishingInterval (Part 4) | None | Next update | - | In 10.1.6, the connector does not read the publishing interval the server accepted, so a change made by the server is not shown. In the next FrameworX update, the connector shows the accepted interval in Module Information > OPC Server Status and writes it to the Device trace. |
SamplingInterval (Part 4) | None | Fixed | 250 ms | The same 250 ms for every point, whatever the Refresh Rate. In the next FrameworX update, the Station gets a Sampling Interval setting, 250 ms by default and not used with Enable Read Polling; when the server revises the requested value, the connector writes the revision to the Device trace. |
QueueSize (Part 4) | None | Fixed | 1 | A change between two publishes replaces the previous one. In the next FrameworX update, the Station gets a Queue Size setting, 1 by default and not used with Enable Read Polling; a larger queue makes the server keep up to that many changes between two publishes. |
DiscardOldest (Part 4) | None | Fixed | True | |
MonitoringMode (Part 4) | None | Fixed | Reporting | |
DataChangeFilter Trigger (Part 4) | None | Fixed | No filter sent | The server applies the specification default, StatusValue. |
DataChangeFilter Deadband (Part 4) | None | Fixed | No filter sent | The tag deadband configured in FrameworX is not sent to the server. |
Lifetime (Part 4) | None | Fixed | 10 min | |
MaxKeepAlive (Part 4) | None | Fixed | 5 s | |
MaxNotificationsPerPublish (Part 4) | None | Fixed | 0 (no limit) | |
Priority (Part 4) | None | Fixed | 0 | |
PublishingEnabled (Part 4) | None | Fixed | True | |
Splitting items into subscriptions | ReadGroupMaxSize (Channel); Use Single OPC Connection; Use Single Read Group | Configurable | 100 (0 to 10000); on; off | By default all items share one subscription, whatever ReadGroupMaxSize is. Read groups become separate subscriptions only with Use Single OPC Connection off. Use Single Read Group is enabled only with polling. |
Data types
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
Scalar types | Tag type | Fixed | - | The tag type sets the conversion. The UNS Tag Provider reports Float, DateTime, UInteger and Guid variables as Text. An Integer tag holds values up to 2,147,483,647, so a UInteger value above it does not fit. In the next FrameworX update, the tag import and the UNS Tag Provider give the same tag type to each OPC UA type (Float becomes Double, DateTime becomes DateTime, UInteger becomes Integer, Guid becomes Guid), and standard and server-specific types derived from a standard type are imported as their base type. A re-import keeps the type of an existing tag. |
Structures, DataTypeDefinition (Part 3) | UserType through Import | Configurable | - | Structures are decoded from their DataTypeDefinition (OPC UA 1.04 or newer). |
Arrays of structures | Import | Configurable | - | Decoded element by element. |
Enumerations | Tag type | Fixed | Int32 | The value arrives as Int32 and is stored as a number in an integer tag. |
DateTime and time zone (Part 6) | None | Fixed | UTC on the wire | Reads convert to local time; writes send UTC. |
FrameworX settings with no direct specification equivalent
FrameworX setting | What it does | Closest specification concept | Notes |
|---|---|---|---|
Backup Station (Node > SecondaryStation) | Switches between the primary and the backup Station when the connection fails. Each Station has its own settings. | Non-transparent redundancy | |
Address without | The namespace is inferred from the first branch under Objects, reading the first 100 references only, so on a server with more nodes under Objects the inference can fail. | NodeId | Always write |
Stalled subscription detection | With no data, tags go Uncertain, the subscription is recreated after 10, 20 and 40 s, and then the session reconnects. The limit is 3 times the largest of 5 s, the Refresh Rate and the granted keep-alive. | Keep-alive and Lifetime | |
AccessType ReadPollingRate | With polling, it is the read cycle. Without polling, it only triggers the session check. | Read | |
AccessType ReadPolling (Never, Always, OnDisplayOrServer) | Never without AcceptUnsolicited: the item is not subscribed. OnDisplayOrServer: only items in use are subscribed, and a change recreates the subscription. | MonitoringMode | |
AccessType ReadOnStartup and ReadTrigger | In subscription mode they only check the session and do not issue a Read. | Read | |
AccessType WriteEvent and WriteTrigger | Decide when a tag change becomes a Write. | Write | |
AcceptUnsolicited | Required to subscribe an item when ReadPolling is Never. | - | |
Use Computer Timestamp | Replaces the source time with the local time of reception. | SourceTimestamp | The device time is not kept. |
Host Override | Rewrites the host or port before connecting. | EndpointUrl | |
Branch Separator | Path separator for string identifiers and the browse tree. | BrowsePath | |
Bit modifier on the point | Reads or writes one bit. A write reads, modifies and writes the whole value. | - | The write is not atomic. |
Use Single Read Group | Puts all points in one read group (polling only). | - |
In this section...