Alarms & Audit-Trail (Tutorial) teaches you to:
- Create alarm groups and items
- Configure alarm conditions
- Set up notifications
- Enable audit trail for FDA 21 CFR Part 11 compliance
Prerequisites:
- Navigate to Alarms → Groups
- Verify pre-defined groups exist:
Group | AckRequired | LogEvents |
---|
Critical | True | True |
Warning | False | True |
AuditTrail | False | True |
Modify Critical group:
- Open the ComboBox Sound field
- Select Exclamation
- Press Enter
2. Create Alarm Items
- Go to Alarms → Items
- Add high temperature alarm:
Property | Value |
---|
TagName | TankFarm/Tank1/Temp |
Condition | HiHi |
Limit | 85 |
Group | Critical |
Message | Tank 1 Critical Temperature: {Tag.TankFarm/Tank1/Temp}°C |
Priority | 100 |
- Add low level alarm:
Property | Value |
---|
TagName | Tag.ankFarm/Tank1/Level |
Condition | Lo |
Limit | 20 |
Group | Warning |
Message | Tank 1 Low Level Warning |
Priority | 50 |
- Navigate to Alarms → Areas
- Create hierarchy:
Assign alarms to areas:
- Return to Alarms → Items
- Set Area =
Plant_Production_Tank1
for both alarms
4. Enable Audit Trail
- Go to Alarms → Global Settings
- In Audit Trail section:
- Check Enable Audit Trail
- Enable options:
- User Logon/Logoff
- Tag Changes
- Operator Actions
- Custom Messages
- Configure database retention:
- Life Time: 2555 days (7 years for FDA compliance)
5. Create Alarm Display
- Navigate to Displays → New
- Name:
AlarmMonitor
- Add AlarmViewer control from toolbox
- Configure properties:
- List: OnlineAlarms
- ShowAcknowledged: False
- Columns: Time, TagName, Message, Value, Group
- Add AlarmArea control for navigation
- Save display
6. Test Alarms
- Start Runtime (Runtime → Startup)
- Open Alarms→ Alarms Monitor
- Simulate alarm conditions by changing tag values
- Verify the alarms showing in the alarm viewer
7. Verify Audit Trail
- Change AlarmViewer List to
AuditTrail
- Verify logged events:
- User login
- Alarm triggers
- Acknowledgments
- Tag changes