Alarms & Audit-Trail (Tutorial) teaches you to:

  • Create alarm groups and items
  • Configure alarm conditions
  • Set up notifications
  • Enable audit trail for FDA 21 CFR Part 11 compliance

Prerequisites:

On this page:



Alarms → Tutorial | Concept | How-to Guide | FDA 21 CRF 11 | Reference



1: Configure Alarm Groups

  1. Navigate to Alarms → Groups
  2. Verify pre-defined groups exist:


GroupAckRequiredLogEvents
CriticalTrueTrue
WarningFalseTrue
AuditTrailFalseTrue


Modify Critical group:

    • Open the ComboBox Sound field
    • Select Exclamation
    • Press Enter

2: Create Alarm Items

  1. Go to Alarms → Items
  2. Add high temperature alarm:
PropertyValue
TagNameTankFarm/Tank1/Temp
ConditionHiHi
Limit85
GroupCritical
MessageTank 1 Critical Temperature: {Tag.TankFarm/Tank1/Temp}°C
Priority100
  1. Add low level alarm:
PropertyValue
TagNameTag.ankFarm/Tank1/Level
ConditionLo
Limit20
GroupWarning
MessageTank 1 Low Level Warning
Priority50

3: Configure Alarm Areas

  1. Navigate to Alarms → Areas
  2. Create hierarchy:
  • Plant
    • Production
      • Tank1
      • Tank2
    • Utilities

Assign alarms to areas:

    • Return to Alarms → Items
    • Set Area = Plant_Production_Tank1 for both alarms

4: Enable Audit Trail

  1. Go to Alarms → Global Settings
  2. In Audit Trail section:
    • Check Enable Audit Trail
    • Enable options:
      • User Logon/Logoff
      • Tag Changes
      • Operator Actions
      • Custom Messages
  3. Configure database retention:
    • Life Time: 2555 days (7 years for FDA compliance)

5: Create Alarm Display

  1. Navigate to Displays → New
  2. Name: AlarmMonitor
  3. Add AlarmViewer control from toolbox
  4. Configure properties:
    • List: OnlineAlarms
    • ShowAcknowledged: False
    • Columns: Time, TagName, Message, Value, Group
  5. Add AlarmArea control for navigation
  6. Save display

6: Test Alarms

  1. Start Runtime (Runtime → Startup)
  2. Open Alarms→ Alarms Monitor
  3. Simulate alarm conditions by changing tag values
  4. Verify the alarms showing in the alarm viewer

7: Verify Audit Trail

  1. Change AlarmViewer List to AuditTrail
  2. Verify logged events:
    • User login
    • Alarm triggers
    • Acknowledgments
    • Tag changes



In this section...