How the OPC UA Client connector maps to the OPC UA specification: which features it exposes, under which name, and which values are fixed.
Connectors Library → Browse By Connector Group → Standard Protocols → OPC UA Client Connector → OPC UA Client Specification Mapping
Overview
This page lists the OPC UA specification items (OPC 10000 series, cited by Part) that matter to a client, and shows how the FrameworX OPC UA Client connector handles each one. It describes FrameworX 10.1.6, driver version 1.1.0.1. Setting names are the ones shown on the Station and Point configuration.
Status values:
- Configurable: you set it in the connector.
- Fixed: the connector uses its own value, with no setting.
- Fixed (automatic): the connector reads the value from the server.
- Library default: the connector does not set it; the default of the embedded OPC UA library applies.
- Not implemented: the specification defines it and the connector does not provide it.
- Not applicable: not needed for the way the connector works.
Specification items
Transport and discovery
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
| Station > URL | Configurable | Free text | The URL is used as typed. |
| None | Not implemented | - | Only |
| None | Not implemented | - | |
Reverse Connect (Part 6) | None | Not implemented | - | The client always opens the connection. |
GetEndpoints (Part 4) | Station > Discovery button | Configurable | Without a port, tries 4840, 49320, 62841, 4845 and 49380 | Designer only. Lists URL, security mode and security policy. |
FindServers (Part 4) | None | Not implemented | - | Only GetEndpoints is used. |
Endpoint selection (Part 4) | Discovery, row selection | Fixed | URL and a security flag | Only the URL is stored. Disable Security is set when the selected row uses mode None. The row's policy and mode are not stored. |
EndpointUrl and DiscoveryUrl (Part 4) | Host Override; Ignore Discovery URL | Configurable | Empty; off | Host Override replaces the host or port before connecting. Ignore Discovery URL keeps the configured address instead of the one the server returns. |
Security
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
Application instance certificate (Parts 4 and 6) | Station > Certificate (Default / Custom) and the certificate generator | Configurable | Key 1024, 2048 or 4096 bits; SHA-1 or SHA-256 | With security on and no certificate, the client does not connect. A server that offers only Basic256Sha256 needs a key of 2048 bits or more and SHA-256. |
Trust list (Parts 2 and 4) | Certificate Default or Custom; trusted, issuers and rejected folders | Configurable | Default | Default trusts an unknown server certificate on the first connection and stores it. Custom accepts only the certificates in the trusted folder. |
SecurityPolicy (Part 7) | Disable Security | Fixed | None, or the best policy the server offers | The policy itself is not selectable. |
Automatic policy selection | None | Library default | The most secure policy the server offers that the client certificate supports | Use a 2048-bit SHA-256 certificate to reach Basic256Sha256 and newer policies. |
MessageSecurityMode (Part 4) | None | Fixed | None, or the best mode the server offers | Sign or SignAndEncrypt cannot be forced. |
Anonymous user token (Part 4) | User Name left empty | Configurable | Default | |
UserName user token (Part 4) | User Name and Password | Configurable | Empty | |
X.509 user token (Part 4) | None | Not implemented | - | |
Issued token, Kerberos (Part 4) | Windows Authentication and Domain | Not implemented | Box off and locked | The option appears on the Station but has no effect at runtime. |
Global Discovery Server, certificate management (Part 12) | None | Not implemented | - |
Session and redundancy
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
Session timeout (Part 4) | None | Fixed | 10 min (600000 ms) | The server can revise the value. |
Reconnection | None | Fixed | Increasing waits up to about 30 s | Reconnection is handled by the connector itself. |
Automatic reconnection by the OPC UA library | None | Not implemented | Off | After a lost connection the connector creates a new session instead of reactivating the old one. |
Session keep-alive (Part 4) | None | Fixed | Status read every 5 s | Each session reads the server's CurrentTime, State, SecondsTillShutdown and ShutdownReason every 5 s. |
Sessions per Node | Use Single OPC Connection | Configurable | On | On: one session for writes and status and another one for the items. Off: one more session and one more subscription per read group. |
Server redundancy, RedundancySupport and ServerUriArray (Part 4) | None | Not implemented | - | Use a backup Station instead (see Backup Station below). |
Addressing
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
NodeId | Point > Address | Configurable | - | |
NodeId in namespace 0, | Point > Address | Configurable | - | In subscription mode these points stay Uncertain. Read them with polling. |
NodeId | Point > Address | Not implemented | - | The GUID text is sent as a string identifier and the server does not find the node. |
ExpandedNodeId | None | Not implemented | - | |
ExpandedNodeId | None | Not implemented | - | |
NamespaceArray, index and URI (Part 5) | Address text | Fixed | Numeric index | With |
MaxNodesPerBrowse (Part 5) | None | Fixed (automatic) | Read from the server | Used to limit Browse calls. |
Browse and continuation points (Part 4) | Designer browse, Import | Fixed | 50 references per call | Namespace discovery issues a single BrowseNext, so it stops at 100 references. |
TranslateBrowsePathsToNodeIds (Part 4) | None | Not implemented | - | The address is always a NodeId. |
RegisterNodes (Part 4) | None | Not implemented | - | |
IndexRange (Part 4) | None | Not implemented | - | Arrays are read or subscribed whole and split in FrameworX. |
Arrays | Point > Modifiers > Array; tag | Configurable | Modifier size | The point on element 0 receives the array and fills the tag elements. A write rewrites the whole array. |
Structure members | Point on a UserType tag; Import address | Configurable | - | Uses the member node, or the decoded field of the parent structure. Writing one member rewrites the whole structure. |
Read and write
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
Read (Part 4) | Enable Read Polling; AccessType | Configurable | Off | Reads at the AccessType rate. |
maxAge (Part 4) | Read From Device | Configurable | Off; on sends maxAge 0 | Applies to single reads. Polled reads always send maxAge 0. |
TimestampsToReturn (Part 4) | None | Fixed | Source for subscriptions; Both for polling and single reads | Session status reads use Neither. |
SourceTimestamp and ServerTimestamp (Part 4) | Use Computer Timestamp | Configurable | Off | Off: scalars and arrays use the SourceTimestamp, structures use the ServerTimestamp. On: the local time of reception. |
StatusCode to quality (Part 4) | Tag quality | Fixed | Bad, Uncertain, Good | Only the severity is kept; sub-codes are not. |
Write (Part 4) | AccessType (WriteEvent, WriteTrigger) | Configurable | - | One node per call, without status or timestamp. One retry on failure. |
Server operation limits (OperationLimits)
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
MaxNodesPerRead (Part 5) | None | Fixed (automatic) | Read from the server; read groups of 75% of the limit | In polling mode, keep ReadGroupMaxSize at or below 75% of the server's MaxNodesPerRead. With a larger read group, some points can receive another point's value. Subscription mode is not affected. |
MaxMonitoredItemsPerCall (Part 5) | None | Fixed (automatic) | Read from the server; 100 when the server does not publish it | Batch size when monitored items are created. |
MaxNodesPerWrite (Part 5) | None | Not applicable | - | The connector writes one node per call. |
Subscriptions and monitored items
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
Subscription or periodic read | Enable Read Polling | Configurable | Off (subscription) | |
PublishingInterval (Part 4) | Refresh Rate | Configurable | 500 ms | Below 250 ms data does not arrive faster, because the sampling interval is fixed at 250 ms. |
Revised PublishingInterval (Part 4) | None | Not implemented | - | The connector does not read the revised value, so a change made by the server is not shown. |
SamplingInterval (Part 4) | None | Fixed | 250 ms | |
QueueSize (Part 4) | None | Fixed | 1 | A change between two publishes replaces the previous one. |
DiscardOldest (Part 4) | None | Fixed | True | |
MonitoringMode (Part 4) | None | Fixed | Reporting | |
DataChangeFilter Trigger (Part 4) | None | Fixed | No filter sent | The server applies the specification default, StatusValue. |
DataChangeFilter Deadband (Part 4) | None | Fixed | No filter sent | The tag deadband configured in FrameworX is not sent to the server. |
EURange and percent deadband (Part 8) | None | Not implemented | - | |
Lifetime (Part 4) | None | Fixed | 10 min | |
MaxKeepAlive (Part 4) | None | Fixed | 5 s | |
MaxNotificationsPerPublish (Part 4) | None | Fixed | 0 (no limit) | |
Priority (Part 4) | None | Fixed | 0 | |
PublishingEnabled (Part 4) | None | Fixed | True | |
Splitting items into subscriptions | ReadGroupMaxSize (Channel); Use Single OPC Connection; Use Single Read Group | Configurable | 100 (0 to 10000); on; off | By default all items share one subscription, whatever ReadGroupMaxSize is. Read groups become separate subscriptions only with Use Single OPC Connection off. Use Single Read Group is enabled only with polling. |
SetTriggering (Part 4) | None | Not implemented | - | |
ModifySubscription and ModifyMonitoredItems (Part 4) | None | Not implemented | - | Any change recreates the subscription. |
TransferSubscriptions and Republish (Part 4) | None | Not implemented | - | After a reconnection the subscription is recreated and the server sends the initial values again. Notifications from the disconnected period are lost. |
AggregateFilter (Part 4) | None | Not implemented | - |
Data types
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
Scalar types | Tag type | Fixed | - | The tag type sets the conversion. |
Structures, DataTypeDefinition (Part 3) | UserType through Import | Configurable | - | Structures are decoded from their DataTypeDefinition (OPC UA 1.04 or newer). |
Arrays of structures | Import | Configurable | - | Decoded element by element. |
Enumerations | Tag type | Fixed | Int32 | The value arrives as Int32 and is stored as a number in an integer tag. |
DateTime and time zone (Part 6) | None | Fixed | UTC on the wire | Reads convert to local time; writes send UTC. |
Other services
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
Method Call (Part 4) | None | Not implemented | - | |
Events and Alarms and Conditions (Part 9) | None | Not implemented | - | |
Historical Access, HistoryRead (Part 11) | None in this connector | Not implemented | - | Use the OPC HDA UA Client connector for historical reads. |
Aggregates (Part 13) | None | Not implemented | - | |
PubSub (Part 14) | None | Not implemented | - |
FrameworX settings with no direct specification equivalent
FrameworX setting | What it does | Closest specification concept | Notes |
|---|---|---|---|
Backup Station (Node > SecondaryStation) | Switches between the primary and the backup Station when the connection fails. Each Station has its own settings. | Non-transparent redundancy | |
Address without | The namespace is inferred from the first branch under Objects. | NodeId | Always write |
Stalled subscription detection | With no data, tags go Uncertain, the subscription is recreated after 10, 20 and 40 s, and then the session reconnects. The limit is 3 times the largest of 5 s, the Refresh Rate and the granted keep-alive. | Keep-alive and Lifetime | |
AccessType ReadPollingRate | With polling, it is the read cycle. Without polling, it only triggers the session check. | Read | |
AccessType ReadPolling (Never, Always, OnDisplayOrServer) | Never without AcceptUnsolicited: the item is not subscribed. OnDisplayOrServer: only items in use are subscribed, and a change recreates the subscription. | MonitoringMode | |
AccessType ReadOnStartup and ReadTrigger | In subscription mode they only check the session and do not issue a Read. | Read | |
AccessType WriteEvent and WriteTrigger | Decide when a tag change becomes a Write. | Write | |
AcceptUnsolicited | Required to subscribe an item when ReadPolling is Never. | - | |
Use Computer Timestamp | Replaces the source time with the local time of reception. | SourceTimestamp | The device time is not kept. |
Host Override | Rewrites the host or port before connecting. | EndpointUrl | |
Ignore Discovery URL | Keeps the configured address instead of the one the server returns. | EndpointUrl | |
Branch Separator | Path separator for string identifiers and the browse tree. | BrowsePath | |
Bit modifier on the point | Reads or writes one bit. A write reads, modifies and writes the whole value. | - | The write is not atomic. |
Use Single Read Group | Puts all points in one read group (polling only). | - |
In this section...