Role-specific learning path for device connectivity, operator interfaces, and process control
Next → Control | IT | Operations | System Integrators
Learning Topics
Control engineers work with
...
PLCs, HMIs, and SCADA systems
...
. This guide navigates you through FrameworX documentation for device connectivity, operator
...
interfaces, and
...
process control.
...
Your Role
...
Primary Focus
...
Essential Pages
...
Advanced Topics
...
Control Engineer
...
Field connectivity
Process Control
...
Solution Lifecycle
P1: UNS Foundation
...
P2: Process Modules
Devices Module
...
Alarms Module
Historian Module
Core Responsibilities:
Table of Contents | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
|
Excerpt |
---|
Understand the Platform and Modules:
Learn by doing:
|
Essential Tutorials:
By PLC Brand, Connectors:
Core Learning:
Common Task | Tutorial/How-to | Reference |
---|---|---|
Connect to PLC | [Devices Connection Tutorials] | [Devices Protocols Reference] |
Import PLC tags | [Solution Import Tags Reference] | [UNS Tags Reference] |
Build motor control | [Displays Symbols Reference] | [Symbols Control Reference] |
Setup tank alarms | [Alarms Module How-to Guide] | [Alarms Items Reference] |
Create trends | [Historian Module Tutorial] | [TrendChart Control Reference] |
Add control logic | [Scripts Module Tutorial] | [Scripts Tasks Reference] |
Week 1: Connect devices → Import tags → Verify communication
Week 2: Build displays → Create symbols → Test visualization
Week 3: Configure alarms → Setup historian → Build trends
Week 4: Add control logic → Implement calculations → Complete project
Documentation:
Examples:
Community:
Page Tree | ||
---|---|---|
|
Allen-Bradley ControlLogix
Ethernet
3000ms
Your PLC IP
0
Code Block |
---|
???????????????????????????????
? Header (Title, Time, Alarms)?
???????????????????????????????
? ?
? Main Process Graphic ?
? (P&ID representation) ?
? ?
???????????????????????????????
? Navigation Bar ?
???????????????????????????????
|
Priority | Range | Color | Response Time | Consequence |
---|---|---|---|---|
Critical | 1-200 | Red | Immediate | Safety shutdown |
High | 201-400 | Orange | 10 minutes | Process upset |
Medium | 401-600 | Yellow | 30 minutes | Efficiency loss |
Low | 601-999 | Blue | Next shift | Maintenance required |
Tank Level Alarm Configuration:
Alarm | Trigger | Priority | Deadband | Delay On | Delay Off |
---|---|---|---|---|---|
HiHi | 95% | 250 | 2% | 5 sec | 3 sec |
Hi | 85% | 400 | 2% | 5 sec | 3 sec |
Lo | 15% | 400 | 2% | 5 sec | 3 sec |
LoLo | 5% | 250 | 2% | 5 sec | 3 sec |
Code Block | ||
---|---|---|
| ||
public void PumpControl()
{
// Read process values
float tankLevel = @Tag.Tank01.Level;
float setpoint = @Tag.Tank01.Setpoint;
bool pumpAvailable = @Tag.Pump01.Available;
// Control logic
if (pumpAvailable)
{
if (tankLevel < (setpoint - 5))
{
@Tag.Pump01.StartCmd = true;
@Tag.Pump01.Speed = CalculateSpeed(tankLevel, setpoint);
}
else if (tankLevel > (setpoint + 2))
{
@Tag.Pump01.StartCmd = false;
}
}
// Alarm generation
if (!pumpAvailable && tankLevel < 10)
{
@Tag.Alarms.LowLevelNoPump = true;
}
}
private float CalculateSpeed(float level, float sp)
{
float error = sp - level;
return Math.Max(30, Math.Min(100, error * 5));
}
|
Component | Configuration |
---|---|
Time Axis | Real-time (last hour), Historical (date range), Resolution (1 sec - 1 day) |
Y-Axes | Primary (0-100%), Secondary (0-150°F), Auto-scale option |
Pens | Multiple process values with distinct colors |
Area | Technique | Benefit |
---|---|---|
Scan Rates | Match process dynamics | Reduce network load |
Display Updates | Limit animations | Improve client performance |
Alarm Deadbands | Prevent chattering | Reduce alarm floods |
Script Efficiency | Avoid loops in expressions | Lower CPU usage |
PLC Type | Protocol | Default Settings |
---|---|---|
Allen-Bradley | EtherNet/IP | Slot 0, RPI 100ms |
Siemens | S7 TCP | Rack 0, Slot 2 |
Modbus Devices | Modbus TCP | Port 502, Unit ID 1 |
Schneider | Modbus TCP | Port 502, Holdings |
Omron | FINS | Port 9600, Node 1 |
Issue | Check | Solution |
---|---|---|
PLC won't connect | IP address, subnet | Verify network settings |
Tags not updating | Point mapping | Check addresses match PLC |
Alarms flooding | Deadband, delays | Adjust alarm settings |
HMI slow | Graphics complexity | Simplify animations |
Trends gaps | Historian settings | Check storage configuration |
...