Generate solutions using MCP Designer

How-to ExamplesFeatureApplication → MCP DesignerWater Treatment Plant AI Designer Example



Info

This example demonstrates the solution Highland Municipal Water Treatment Plant created by the MCP for Designer.

Solution download: Highland_WTPWater Treatment Plant AI Designer Example.dbsln

 Technical Technical Specification PDF: Highland_WTP_Equipment_Spec.pdf

L5K PLC Program: Highland_WTP_Main.L5K


Table of Contents
maxLevel2
minLevel2
excludeOverview
stylenone
classon-this-page
printablefalse





Summary

This page contains the technical details for the Act 1 live demo. The AI reads the attached PDF specification and L5K PLC tag database to build the complete SCADA solution.


Demo Prompt

Info

Build a NEW FrameworX solution for the Highland Municipal Water Treatment Plant.

The plant specifications are in the attached PDF, the PLC program is in the attached L5K file.

Create the UNS following ISA-95 standards. Map the PLC points using ControlLogix driver, and add a value simulator protocol for our tests.

Add alarms based on the compliance limits in the spec and set up historian for all process variables.

Create a 3 x 2 dashboard, with Gauges on first rows, and trend, alarm, data grid on second.

Analyze which variables that would benefit from machine learning, for later implementation.

Start everything up and give me a status summary.

Attached documents with the prompt

  1. Highland_WTP_Equipment_Spec.pdf — Professional spec with equipment lists, compliance limits, process notes

  2. Highland_WTP_Main.L5K — ControlLogix tag export with 3 UDTs, all controller tags by area, 3 program stubs

Approximately creation = 7 minutes.


Plant Overview

Highland Municipal Water Treatment Plant is a conventional surface water treatment facility serving approximately 18,000 residents. The plant treats raw water from Highland Reservoir with a design capacity of 5 MGD (million gallons per day) and an average daily production of 3.2 MGD.

Area

Name

Description

100

Raw Water Intake

Reservoir intake structure with raw water pumping

200

Chemical Feed

Coagulant, chlorine, and fluoride chemical storage and dosing

500

Filtration

Four dual-media gravity filters with automated backwash

600

Disinfection & Clearwell

Chlorine contact basin and 0.5 MG clearwell



Control System Architecture

Main Treatment Plant PLC

Parameter

Value

Processor

1756-L83E CompactLogix

IP Address

192.168.1.10

Slot

0

I/O Chassis

1756-A13 (13-slot)

Program File

Highland_WTP_Main.L5K

All treatment plant process variables are available as Controller Tags in the ControlLogix program.



User Defined Types (from L5K)

The L5K file contains 3 UDTs that the AI should recreate as FrameworX User Types:

UDT_Pump

Member

Type

Description

Running

BOOL

Pump running feedback

Fault

BOOL

Pump fault/alarm

Ready

BOOL

Pump ready status

AutoManual

BOOL

0=Manual 1=Auto

SpeedCmd

REAL

Speed command 0-100%

SpeedFeedback

REAL

Speed feedback 0-100%

MotorCurrent

REAL

Motor current in Amps

RunHours

REAL

Accumulated run hours


UDT_ChemPump

Member

Type

Description

Running

BOOL

Pump running feedback

Fault

BOOL

Pump fault/alarm

AutoManual

BOOL

0=Manual 1=Auto

DoseRate

REAL

Current dose rate mL/min

DoseSetpoint

REAL

Dose rate setpoint mL/min

TankLevel

REAL

Chemical tank level %

TotalChemUsed

REAL

Totalizer gallons used

FlowPaced

BOOL

1=Flow-paced 0=Manual rate


UDT_Filter

Member

Type

Description

InService

BOOL

Filter in service

Backwashing

BOOL

Backwash in progress

HeadLoss

REAL

Differential pressure PSI

EffluentTurbidity

REAL

Effluent turbidity NTU

ValvePosition

REAL

Effluent valve 0-100%

TimeSinceBackwash

REAL

Hours since last backwash

BackwashCount

DINT

Cumulative backwash count



Equipment List by Process Area

Area 100 — Raw Water Intake

Tag

Equipment

Description

P-101

Raw Water Pump 1

100 HP VFD centrifugal, 2500 GPM

P-102

Raw Water Pump 2

100 HP VFD centrifugal, 2500 GPM (standby)

FT-101

Flow Transmitter

Magnetic flow meter, raw water header

AIT-101

Turbidity Analyzer

Raw water turbidity, Hach 1720E

AIT-102

pH Analyzer

Raw water pH, Hach pHD sc

LT-101

Level Transmitter

Intake wet well level


Area 200 — Chemical Feed

Tag

Equipment

Description

P-201

Coagulant Pump

Metering pump, aluminum sulfate (alum)

P-202

Pre-Chlorine Pump

Metering pump, sodium hypochlorite

P-203

Fluoride Pump

Metering pump, hydrofluosilicic acid

LT-201

Coagulant Tank Level

2,500 gallon poly tank

LT-202

Hypochlorite Tank Level

5,000 gallon poly tank

LT-203

Fluoride Tank Level

1,500 gallon poly tank


Area 500 — Filtration

Four identical dual-media (anthracite/sand) gravity filters. Tag pattern: FILT{n} where n = 1–4.

Tag Pattern

Description

Type

FILT{n}_HeadLoss

Filter differential pressure

Analog, 0-10 PSI

FILT{n}_Turbidity

Filtered effluent turbidity

Analog, 0-5 NTU

FILT{n}_InService

Filter in-service status

Digital

FILT{n}_Backwashing

Backwash in progress

Digital

FILT{n}_Valve

Effluent valve position

Analog, 0-100%

Backwash trigger: HeadLoss > 8.0 PSI or operator-initiated. Cycle: ~15 min. Only one filter may backwash at a time.


Area 600 — Disinfection & Clearwell

Tag

Equipment

Description

AIT-601

Free Chlorine Analyzer

Post-chlorination residual, Hach CL17sc

AIT-602

pH Analyzer

Finished water pH, Hach pHD sc

AIT-603

Turbidity Analyzer

Finished water turbidity, Hach TU5400sc

LT-601

Clearwell Level

0.5 MG clearwell, ultrasonic level



Water Quality Compliance Limits

Per TCEQ and EPA Surface Water Treatment Rule:

Parameter

Tag

Warn Lo

Warn Hi

Crit Lo

Crit Hi

Unit

Finished Water Turbidity

AIT-603


0.3


1.0

NTU

Filter Turbidity (each)

FILT{n}


0.15


0.5

NTU

Free Chlorine Residual

AIT-601

0.2

3.5

0.1

4.0

mg/L

Finished Water pH

AIT-602

6.5

8.5

6.0

9.0


Clearwell Level

LT-601

25%

95%

15%

98%

%

Chemical Tank Levels

LT-201,2,3

15%


10%


%



Process Notes for SCADA Configuration

  1. Chemical Dosing: Coagulant (alum) dose rate is flow-paced from FT-101. Pre-chlorination is operator-adjusted. Fluoride is flow-paced with manual trim.

  2. Filter Backwash: Only one filter may backwash at a time. Sequence takes ~15 minutes. Remaining three filters handle full plant flow.

  3. ML Opportunity: Filter headloss rate and post-sedimentation turbidity are early indicators of raw water quality changes. Predictive monitoring could enable proactive chemical dose adjustment.

  4. Historian Requirements: All analog process variables historized with appropriate deadband. Digital status on-change. Minimum 1-year retention for regulatory compliance.



Data Source Strategy for the Demo

Source

Status

Purpose

Value Simulator

ENABLED

Drives all live data during demo — makes dashboard come alive

Allen-Bradley ControlLogix

Configured, channel DISABLED

Shows AI correctly mapped tags from L5K file (no physical PLC)



In this section...