Connect to a Modbus Device and addresses to tags.

TutorialsDevices| Tutorial | How-to Guide | Reference


This Tutorial Teaches

(Tutorial) teaches

you to:

  • Configure communication channels
  • Add device nodes
  • Map device addresses to tags
  • Monitor communication status

Prerequisites

:

In this page:

Table of Contents
maxLevel2
minLevel2
indent10px
excludeStepsTeaches
stylenone


  Devices →  Tutorial | Concept | How-to Guide | ReferenceCreate

1. Create Device Channel

  1. Navigate to Devices → ChannelsProtocols
  2. Select Modbus
  3. Click on New Add new channel:
    • Channel Name: ModbusChannel
    • Protocol: Modbus Master ProtocolSettings:
    • Interface: TCP/IP
    • Port: 502
    • Timeout: 3000ms

2. Add Device Node

  1. Go to Devices → Nodes
  2. Create node:
    • Name: PLC1
    • Channel: ModbusChannel
    • Station: IP Address (use 127.0.0.1 for simulator)
    • Port 502
    • Device ID: 1

3. Create Device Points

  1. Navigate to Devices → Points
  2. Add points:

Digital Input:

  • Tag Name: PLC1_DI_001 TankFarm/Tank1/Level
  • Node: PLC1
  • Address: 10001 (Modbus coil) 40001 
  • Data Type: DigitalNative
  • AccessType: ReadWrite

Analog Input:

  • Name: PLC1_AI_001 TankFarm/Tank2/Level
  • Node: PLC1
  • Address: 30001 (Modbus input register) 40002 
  • Data Type: IntegerNativeScaling
  • AccessType:
  • Enable if needed

Map Devices Points to Tags

  1. Go to Unified Namespace → Tags
  2. Select existing tag: PLC1_AI_001
  3. In Address column: N0001
  • ReadWrite

4. Starting Modbus Device Simulator

For testing without real hardware:

  1. Devices → Protocols Channels
  2. Select ModbusChannel
  3. Run Modbus Start Simulator
  4. Monitor values, input values

5. Test Communication

  1. Start Runtime (F5)
  2. Open Devices → Monitor
  3. Check status :
    • Green = Connected
    • Red = Error
    • Yellow = Timeout

Troubleshooting

IssueCheck
No connectionFirewall, IP address, port
Wrong valuesAddress offset, data type
IntermittentTimeout settings, network
No updatesPolling rate, scan groups

Next Steps

  • [Connect to a PLC] - Specific PLC brands
  • [Define Alarms] - Alarm on device values
  • [Historian] - Log device data
    1. (if the ActivityCounter is increasing and LastErrorCode stays fixed, it means everything is running properly)