This page lists the OPC UA specification items (OPC 10000 series, cited by Part) that matter to a client, and shows how the FrameworX OPC UA Client connector handles each one. It describes the released FrameworX 10.1.6 (Update 6a), OPC UA Client driver version 1.1.0.1. Sentences that start with "In the next FrameworX update" describe changes planned for the next update; until it is installed, the connector behaves as the rest of the row describes. Setting names are the ones shown on the Station and Point configuration.

...

  • Configurable: you set it in the connector.
  • Fixed: the connector uses its own value, with no setting.
  • Fixed (automatic): the connector reads the value from the server.
  • Library default: the connector does not set it; the default of the embedded OPC UA library applies.
  • Not implemented: the specification defines it and the connector does not provide it.
  • Not applicable: not needed for the way the connector worksNext update: not available in 10.1.6; planned for the next FrameworX update.

Specification items

Transport and discovery

Specification term

FrameworX setting

Status

Value or default

Notes

opc.tcp (Part 6)

Station > URL

Configurable

Free text

The URL is used as typed.

opc.https (Part 6)

None

Not implemented

-

Only opc.tcp is supported. With an A URL with another scheme (opc.https:// or https:// URL the connector opens no connection and the points stay Uncertain.

opc.wss, WebSockets (Part 6)

None

Not implemented

-

Reverse Connect (Part 6)

None

Not implemented

-

The client always opens the connectionhttps, https, opc.wss or http) is changed by the station editor into an invalid opc.tcp address, and the connection fails without a specific message. In the next FrameworX update, such a URL is refused with a clear message, in the station editor and at runtime, and the editor keeps it as typed.

GetEndpoints (Part 4)

Station > Discovery button

Configurable

Without a port, tries 4840, 49320, 62841, 4845 and 49380

Designer only. Lists URL, security mode and security policy of the endpoints the server returns. In the next FrameworX update, only opc.tcp endpoints are listed.

FindServers (Part 4)

None

Station > Discovery button

Next updateNot implemented

-Only

GetEndpoints is usedIn 10.1.6, Discovery uses GetEndpoints only. In the next FrameworX update, Discovery also asks each server it reaches for the servers it knows and lists their opc.tcp endpoints. Designer only.

Endpoint selection (Part 4)

Discovery, row selection

Fixed

URL and a security flag

Only the URL is stored. Disable Security is set when the selected row uses mode None. The row's policy and mode are not stored.

EndpointUrl and DiscoveryUrl (Part 4)

Host Override; Ignore Discovery URL

Configurable

Empty; off

Host Override replaces the host or port before connecting. Ignore Discovery URL keeps the configured address instead of the one the server returns.

Security

Specification term

FrameworX setting

Status

Value or default

Notes

Application instance certificate (Parts 4 and 6)

Station > Certificate (Default / Custom); key and hash in the Designer certificate generator

Configurable

Key 1024 (default), 2048 or 4096 bits; SHA-1 (default) or SHA-256

The key size and the hash are chosen in the Designer certificate generator, not on the Station. With security on and no certificate, the client does not connect and keeps retrying, without a message that names the certificate. In the next FrameworX update, the Devices trace and the station status name the missing certificate, where it is expected and how to create it with the Certificate button of the Station. A server that offers only Basic256Sha256 needs a key of 2048 bits or more and SHA-256.

Trust list (Parts 2 and 4)

Certificate Default or Custom; trusted, issuers and rejected folders

Configurable

Default

Default trusts an unknown server certificate on the first connection and stores it. Custom accepts only the certificates in the trusted folder.

SecurityPolicy (Part 7)

Disable Security

Fixed

None, or the best policy the server offers

The policy itself is not selectable.

Automatic policy selection

None

Library default

The most secure policy the server offers that the client certificate supports

Use a 2048-bit SHA-256 certificate to reach Basic256Sha256 and newer policies. When the server advertises its endpoints on a port other than the one the Station uses (Host Override, NAT or port mapping), the connector takes the first endpoint the server lists.

MessageSecurityMode (Part 4)

None

Fixed

None, or the best mode the server offers

Sign or SignAndEncrypt cannot be forced.

Anonymous user token (Part 4)

User Name left empty

Configurable

Default

UserName user token (Part 4)

User Name and Password

Configurable

Empty

X.509 user token (Part 4)

None

Not implemented

-

Issued token, Kerberos (Part 4)

Windows Authentication and Domain

Not implemented

Box off and locked

The option appears on the Station but has no effect at runtime.

Global Discovery Server, certificate management (Part 12)

None

Not implemented

-

Session

...

Specification term

FrameworX setting

Status

Value or default

Notes

Session timeout (Part 4)

NoneFixed

Library default

10 min (600000 ms)

The server can revise the value.

Reconnection

None

FixedIncreasing

waits up to about 30 s2, 4, 8, 16 and then 30 s (from 10.1.6)

Reconnection is handled by the connector itself.

Automatic reconnection by the OPC UA library

None

Not implemented

Off

After a lost connection the connector creates a new session instead of reactivating the old one.

Session keep-alive (Part 4)

NoneFixed

Library default

Status read every 5 s

Each session reads the server's CurrentTime, State, SecondsTillShutdown and ShutdownReason every 5 s.

Sessions per Node

Use Single OPC Connection

Configurable

On

On: one session for writes and status and another one for the items. Off: one more session and one more subscription per read group.

Server redundancy, RedundancySupport and ServerUriArray (Part 4)

None

Not implemented

-

Use a backup Station instead (see Backup Station below).

Addressing

Specification term

FrameworX setting

Status

Value or default

Notes

NodeId i=, s=, b= (Part 6)

Point > Address

Configurable

-

NodeId in namespace 0, ns=0;... (Part 6)

Point > Address

Configurable

-

In subscription mode these points stay Uncertain. Read them with polling; read them with Enable Read Polling. In the next FrameworX update, they also update in subscription mode.

NodeId g=, GUID (Part 6)

Point > Address

Not implementedNext update

-

The In 10.1.6, the GUID text is sent as a string identifier and the server does not find the node, so a point with a g= address does not read or write, including one created by the tag import. In the next FrameworX update, points with a g= address read and write their values. For a node whose identifier is text, use s=, not g=.

ExpandedNodeId nsu= (Part 6)

None

Not implemented

-

Point > Address

Next update

-

Not supported in 10.1.6. In the next FrameworX update, a point addressed with nsu= follows the namespace URI, so it keeps its node when the server reorders its namespaces.

ExpandedNodeId svr= (Part 6)

None

Not implemented

Point > Address

Next update

-

Not supported in 10.1.6. In the next FrameworX update, svr=0 (the server of the Station) is accepted, and an address that names another server is refused with a message.-

NamespaceArray, index and URI (Part 5)

Address text

Fixed

Numeric index

With ns= the address stores the namespace index. If the server reorders its namespaces, the point targets another node or fails. In the next FrameworX update, an address with nsu= follows the namespace URI instead.

MaxNodesPerBrowse (Part 5)

None

Fixed (automatic)

Read from the server

Used to limit Browse calls.

Browse and continuation points (Part 4)

Designer browse, Import

Fixed

50 references per call

Namespace discovery issues a single BrowseNext, so it stops at 100 references.

TranslateBrowsePathsToNodeIds (Part 4)

None

Not implemented

-

The address is always a NodeId.

RegisterNodes (Part 4)

None

Not implemented

-

IndexRange (Part 4)

None

Not implemented

-

Arrays are read or subscribed whole and split in FrameworX.

It does not change how the connector browses.

Arrays

Arrays

Point > Modifiers > Array; tag Item[0]

Configurable

Modifier size

The point on element 0 receives the array and fills the tag elements. A write rewrites the whole array.

Structure members

Point on a UserType tag; Import address

Configurable

-

Uses the member node, or the decoded field of the parent structure. Writing one member rewrites the whole structure. Structures received by subscription show Good quality and the time of reception, not the quality and timestamp sent by the server. In the next FrameworX update, the Station option Structure Server Status (off by default) makes them take the quality and the source timestamp sent by the server.

Read and write

Specification term

FrameworX setting

Status

Value or default

Notes

Read (Part 4)

Enable Read Polling; AccessType

Configurable

Off

Reads at the AccessType rate.

maxAge (Part 4)

Read From Device

Configurable

Off; on sends maxAge 0

Applies The setting applies to single reads only. Polled reads always send maxAge 0, so they always read from the device. In the next FrameworX update, Read From Device is on by default and polled reads follow it too: on reads from the device, off lets the server answer from its cache. A node saved in 10.1.6 keeps reading from the device.

TimestampsToReturn (Part 4)

None

Fixed

Source for subscriptions; Both for polling and single reads

Session status reads use Neither.

SourceTimestamp and ServerTimestamp (Part 4)

Use Computer Timestamp

Configurable

Off

Off: scalars and arrays use the SourceTimestamp, ; structures received by subscription use the ServerTimestamptime of reception. On: the local time of reception.

StatusCode to quality (Part 4)

Tag quality

Fixed

Bad, Uncertain, Good

Only the severity is kept; sub-codes are not.

Write (Part 4)

AccessType (WriteEvent, WriteTrigger)

Configurable

-

One node per call, without status or timestamp. One retry on failure.

...

Specification term

FrameworX setting

Status

Value or default

Notes

MaxNodesPerRead (Part 5)

None

Fixed (automatic)

Read from the server; read groups of 75% of the limit

In polling mode, keep ReadGroupMaxSize at or below 75% of the server's MaxNodesPerRead. With a larger read group, some points can receive another point's value. Subscription mode is not affectedIn the next FrameworX update, every point receives its own value, whatever the read group size.

MaxMonitoredItemsPerCall (Part 5)

None

Fixed (automatic)

Read from the server; 100 when the server does not publish it

Batch size when monitored items are created.

MaxNodesPerWrite (Part 5)

None

Not applicable

-

The connector writes one node per call.

Subscriptions and monitored items

Specification term

FrameworX setting

Status

Value or default

Notes

Subscription or periodic read

Enable Read Polling

Configurable

Off (subscription)

PublishingInterval (Part 4)

Refresh Rate

Configurable

500 ms

Below 250 ms data Data does not arrive faster with a Refresh Rate below 250 ms, because the sampling interval is fixed at 250 ms.

Revised PublishingInterval (Part 4)

NoneNot

implementedNext update

-

The In 10.1.6, the connector does not read the revised valuethe publishing interval the server accepted, so a change made by the server is not shown. In the next FrameworX update, the connector shows the accepted interval in Module Information > OPC Server Status and writes it to the Device trace.

SamplingInterval (Part 4)

None

Fixed

250 ms

The same 250 ms for every point, whatever the Refresh Rate. In the next FrameworX update, the Station gets a Sampling Interval setting, 250 ms by default and not used with Enable Read Polling; when the server revises the requested value, the connector writes the revision to the Device trace.

QueueSize (Part 4)

None

Fixed

1

A change between two publishes replaces the previous one. In the next FrameworX update, the Station gets a Queue Size setting, 1 by default and not used with Enable Read Polling; a larger queue makes the server keep up to that many changes between two publishes.

DiscardOldest (Part 4)

None

Fixed

True

MonitoringMode (Part 4)

None

Fixed

Reporting

DataChangeFilter Trigger (Part 4)

None

Fixed

No filter sent

The server applies the specification default, StatusValue.

DataChangeFilter Deadband (Part 4)

None

Fixed

No filter sent

The tag deadband configured in FrameworX is not sent to the server.

EURange and percent deadband (Part 8)

None

Not implemented

-

Lifetime (Part 4)

None

Fixed

10 min

MaxKeepAlive (Part 4)

None

Fixed

5 s

MaxNotificationsPerPublish (Part 4)

None

Fixed

0 (no limit)

Priority (Part 4)

None

Fixed

0

PublishingEnabled (Part 4)

None

Fixed

True

Splitting items into subscriptions

ReadGroupMaxSize (Channel); Use Single OPC Connection; Use Single Read Group

Configurable

100 (0 to 10000); on; off

By default all items share one subscription, whatever ReadGroupMaxSize is. Read groups become separate subscriptions only with Use Single OPC Connection off. Use Single Read Group is enabled only with polling.

SetTriggering (Part 4)

None

Not implemented

-

ModifySubscription and ModifyMonitoredItems (Part 4)

None

Not implemented

-

Any change recreates the subscription.

TransferSubscriptions and Republish (Part 4)

None

Not implemented

-

After a reconnection the subscription is recreated and the server sends the initial values again. Notifications from the disconnected period are lost.

AggregateFilter (Part 4)

None

Not implemented

-

Data types

Specification term

FrameworX setting

Status

Value or default

Notes

Scalar types

Tag type

Fixed

-

The tag type sets the conversion. The UNS Tag Provider reports Float, DateTime, UInteger and Guid variables as Text. An Integer tag holds values up to 2,147,483,647, so a UInteger value above it does not fit. In the next FrameworX update, the tag import and the UNS Tag Provider give the same tag type to each OPC UA type (Float becomes Double, DateTime becomes DateTime, UInteger becomes Integer, Guid becomes Guid), and standard and server-specific types derived from a standard type are imported as their base type. A re-import keeps the type of an existing tag.

Structures, DataTypeDefinition (Part 3)

UserType through Import

Configurable

-

Structures are decoded from their DataTypeDefinition (OPC UA 1.04 or newer).

Arrays of structures

Import

Configurable

-

Decoded element by element.

Enumerations

Tag type

Fixed

Int32

The value arrives as Int32 and is stored as a number in an integer tag.

DateTime and time zone (Part 6)

None

Fixed

UTC on the wire

Reads convert to local time; writes send UTC.

Other services

Specification term

FrameworX

...

Status

...

Value or default

...

Notes

...

Method Call (Part 4)

...

None

...

Not implemented

...

-

...

Events and Alarms and Conditions (Part 9)

...

None

...

Not implemented

...

-

...

Historical Access, HistoryRead (Part 11)

...

None in this connector

...

Not implemented

...

-

...

Use the OPC HDA UA Client connector for historical reads.

...

Aggregates (Part 13)

...

None

...

Not implemented

...

-

...

PubSub (Part 14)

...

None

...

Not implemented

...

-

FrameworX settings with no direct specification equivalent

FrameworX setting

What it does

Closest specification concept

Notes

Backup Station (Node > SecondaryStation)

Switches between the primary and the backup Station when the connection fails. Each Station has its own settings.

Non-transparent redundancy

Address without ns=

The namespace is inferred from the first branch under Objects, reading the first 100 references only, so on a server with more nodes under Objects the inference can fail. i=2258 without ns= becomes a string identifier. In the next FrameworX update, the inference reads past 100 references.

NodeId

Always write ns= in the address.

Stalled subscription detection

With no data, tags go Uncertain, the subscription is recreated after 10, 20 and 40 s, and then the session reconnects. The limit is 3 times the largest of 5 s, the Refresh Rate and the granted keep-alive.

Keep-alive and Lifetime

AccessType ReadPollingRate

With polling, it is the read cycle. Without polling, it only triggers the session check.

Read

AccessType ReadPolling (Never, Always, OnDisplayOrServer)

Never without AcceptUnsolicited: the item is not subscribed. OnDisplayOrServer: only items in use are subscribed, and a change recreates the subscription.

MonitoringMode

AccessType ReadOnStartup and ReadTrigger

In subscription mode they only check the session and do not issue a Read.

Read

AccessType WriteEvent and WriteTrigger

Decide when a tag change becomes a Write.

Write

AcceptUnsolicited

Required to subscribe an item when ReadPolling is Never.

-

Use Computer Timestamp

Replaces the source time with the local time of reception.

SourceTimestamp

The device time is not kept.

Host Override

Rewrites the host or port before connecting.

EndpointUrl

Ignore Discovery URL

Keeps the configured address instead of the one the server returns.

EndpointUrl

Branch Separator

Path separator for string identifiers and the browse tree.

BrowsePath

Bit modifier on the point

Reads or writes one bit. A write reads, modifies and writes the whole value.

-

The write is not atomic.

Use Single Read Group

Puts all points in one read group (polling only).

-

...