This page lists the OPC UA specification items (OPC 10000 series, cited by Part) that matter to a client, and shows how the FrameworX OPC UA Client connector handles each one. It describes FrameworX 10.1.6, driver version 1.1.0.1. Rows marked from 10.1.7 describe changes in FrameworX 10.1.7, driver version 1.1.0.6. Setting names are the ones shown on the Station and Point configuration.
...
Specification term | FrameworX setting | Status | Value or default | Notes | ||
|---|---|---|---|---|---|---|
NodeId | Point > Address | Configurable | - | |||
NodeId in namespace 0, | Point > Address | Configurable | - | In subscription mode these points stay Uncertain. Read them with polling. | ||
NodeId | Point > Address | Not implemented | - | Configurable (from 10.1.7) | - | From 10.1.7, points with a |
ExpandedNodeId | None | Not implemented | - | |||
ExpandedNodeId | None | Not implemented | Point > Address (from 10.1.7) | Configurable (from 10.1.7) |
| From 10.1.7, |
NamespaceArray, index and URI (Part 5) | Address text | Fixed | Numeric index | With | ||
MaxNodesPerBrowse (Part 5) | None | Fixed (automatic) | Read from the server | Used to limit Browse calls. | ||
Browse and continuation points (Part 4) | Designer browse, Import | Fixed | 50 references per call | Namespace discovery issues a single BrowseNext, so it stops at 100 references. | ||
TranslateBrowsePathsToNodeIds (Part 4) | None | Not implemented | - | The address is always a NodeId. | ||
RegisterNodes (Part 4) | None | Not implemented | - | |||
IndexRange (Part 4) | None | Not implemented | - | Arrays are read or subscribed whole and split in FrameworX. | ||
Arrays | Point > Modifiers > Array; tag | Configurable | Modifier size | The point on element 0 receives the array and fills the tag elements. A write rewrites the whole array. | ||
Structure members | Point on a UserType tag; Import address | Configurable | - | Uses the member node, or the decoded field of the parent structure. Writing one member rewrites the whole structure. From 10.1.7, the Station option Structure Server Status (off by default) makes structures received by subscription take the quality and the source timestamp sent by the server; with it off, they show Good quality and the time of reception. |
Read and write
Specification term | FrameworX setting | Status | Value or default | Notes |
|---|---|---|---|---|
Read (Part 4) | Enable Read Polling; AccessType | Configurable | Off | Reads at the AccessType rate. |
maxAge (Part 4) | Read From Device | Configurable | Off; on sends maxAge 0 | Applies to single reads. Polled reads always send maxAge 0. |
TimestampsToReturn (Part 4) | None | Fixed | Source for subscriptions; Both for polling and single reads | Session status reads use Neither. |
SourceTimestamp and ServerTimestamp (Part 4) | Use Computer Timestamp | Configurable | Off | Off: scalars and arrays use the SourceTimestamp, ; structures received by subscription use the ServerTimestamptime of reception unless Structure Server Status is on (from 10.1.7). On: the local time of reception. |
StatusCode to quality (Part 4) | Tag quality | Fixed | Bad, Uncertain, Good | Only the severity is kept; sub-codes are not. |
Write (Part 4) | AccessType (WriteEvent, WriteTrigger) | Configurable | - | One node per call, without status or timestamp. One retry on failure. |
...
Specification term | FrameworX setting | Status | Value or default | Notes | |||
|---|---|---|---|---|---|---|---|
Subscription or periodic read | Enable Read Polling | Configurable | Off (subscription) | ||||
PublishingInterval (Part 4) | Refresh Rate | Configurable | 500 ms | Below 250 ms Before 10.1.7, data does not arrive faster below 250 ms, because the sampling interval is fixed at 250 ms. From 10.1.7, the Sampling Interval of the Station sets the sampling interval. | |||
Revised PublishingInterval (Part 4) | None | Not implemented | - | Module Information > OPC Server Status; Device trace (from 10.1.7) | Fixed (automatic) (from 10.1.7) | Read from the server | From 10.1.7, the connector reads the publishing interval the server accepted, shows it in the OPC Server Status panel and writes it to the Device trace. Before 10.1.7, the revised value was not readThe connector does not read the revised value, so a change made by the server is was not shown. |
SamplingInterval (Part 4) | None | Fixed | ) | Station > Sampling Interval (from 10.1.7) | Configurable (from 10.1.7) | 250 ms | Before 10.1.7, fixed at 250 ms. Not used with Enable Read Polling. The server can revise the requested value; the connector writes the revision to the Device trace.250 ms |
QueueSize (Part 4) | None | Station > Queue Size (from 10.1.7) | Configurable (from 10.1.7)Fixed | 1 | A With 1, a change between two publishes replaces the previous one. A larger queue makes the server keep up to that many changes between two publishes. Before 10.1.7, fixed at 1. Not used with Enable Read Polling. | ||
DiscardOldest (Part 4) | None | Fixed | True | ||||
MonitoringMode (Part 4) | None | Fixed | Reporting | ||||
DataChangeFilter Trigger (Part 4) | None | Fixed | No filter sent | The server applies the specification default, StatusValue. | |||
DataChangeFilter Deadband (Part 4) | None | Fixed | No filter sent | The tag deadband configured in FrameworX is not sent to the server. | |||
EURange and percent deadband (Part 8) | None | Not implemented | - | ||||
Lifetime (Part 4) | None | Fixed | 10 min | ||||
MaxKeepAlive (Part 4) | None | Fixed | 5 s | ||||
MaxNotificationsPerPublish (Part 4) | None | Fixed | 0 (no limit) | ||||
Priority (Part 4) | None | Fixed | 0 | ||||
PublishingEnabled (Part 4) | None | Fixed | True | ||||
Splitting items into subscriptions | ReadGroupMaxSize (Channel); Use Single OPC Connection; Use Single Read Group | Configurable | 100 (0 to 10000); on; off | By default all items share one subscription, whatever ReadGroupMaxSize is. Read groups become separate subscriptions only with Use Single OPC Connection off. Use Single Read Group is enabled only with polling. | |||
SetTriggering (Part 4) | None | Not implemented | - | ||||
ModifySubscription and ModifyMonitoredItems (Part 4) | None | Not implemented | - | Any change recreates the subscription. | |||
TransferSubscriptions and Republish (Part 4) | None | Not implemented | - | After a reconnection the subscription is recreated and the server sends the initial values again. Notifications from the disconnected period are lost. | |||
AggregateFilter (Part 4) | None | Not implemented | - |
...