| Page properties | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| ||||||||||||
|
Devices compatible with Mitsubishi FX3U
This document has only the specific information about the device connection settings and its address syntax.
Refer to the User Guide for more information on the Device Module or on UNS TagProvider Connections.
On this page:
| Table of Contents | ||||||
|---|---|---|---|---|---|---|
|
Communication Driver Information
Driver name
MitsubishiFXSerial
Assembly Name
T.ProtocolDriver.MitsubishiFXSerial
Assembly Version
On this page:
| Table of Contents | ||||||
|---|---|---|---|---|---|---|
|
Communication with devices compatible with Mitsubishi FX3U
Available for Linux
False
Devices supported
FX3U
Manufacturer
Mitsubishi
Protocol
Proprietary
PC Requirements
Operand | Read | Write | Data Type | Address size |
D - Data register | Yes | Yes | Word | 2 bytes |
TN – Timer Current value | Yes | Yes | Word | 2 bytes |
TS – Timer Contact | Yes | No | Bit | 1 bit |
CN – Counter Current value | Yes | Yes | Word | 2 bytes |
CS – Counter Contact | Yes | No | Bit | 1 bit |
X - Input relay | Yes | No | Bit | 1 bit |
Y - Output relay | Yes | Yes | Bit | 1 bit |
M - Internal relay | Yes | Yes | Bit | 1 bit |
S0 - Annunciator | Yes | Yes | Bit | 1 bit |
Maximum size of blocks: Defines the maximum of addresses in a read block.
The syntax for the Mitsubishi FX Serial communication points is: <Operand> <Address>
Where :
Operand |
|---|
D - Data register |
TN – Timer Current value |
TS – Timer Contact |
CN – Counter Current value |
CS – Counter Contact |
X - Input relay |
Y - Output relay |
M - Internal relay |
S0 - Annunciator |
Note: The Y Operand is an Octal Numeral System.
MitsubishiFX_Serial Revision History | |
|---|---|
Version | Notes |
1.0.1.0 | Initial release on new documentation standards |
In this section:
| Page Tree | ||||
|---|---|---|---|---|
|