Alarm Items (Reference) define individual tags or expressions monitored for alarm conditions within your FrameworX solution. Alarm Items are the fundamental alarm objects that:
- Monitor tag values against configured conditions
- Trigger alarm events when conditions are met
- Associate with AlarmGroups for shared behaviors
- Organize within AlarmAreas for hierarchical structure
- Support multiple limit values for shift-based operations
Each Alarm Item represents a single monitored condition that generates alarms based on your defined thresholds and settings.
Two Alarm Items on the same tag and condition are not supported, because the tag keeps one link per condition: both rows raise alarms, but Tag.<name>.<Condition> and the saved limits follow only one of them.
Configuration Properties
| Property | Description | Required |
|---|---|---|
| TagName | The tag being monitored for alarm events | Yes |
| Condition | Trigger condition (Hi, Lo, RateOfChange, etc.) | Yes |
| Limit | Primary threshold value | Yes |
| Limit1 | Secondary threshold (for shift-based limits) | No |
| Limit2 | Tertiary threshold (for shift-based limits) | No |
| Group | Associated AlarmGroup for shared properties | Yes |
| Area | AlarmArea for hierarchical organization | No |
| Priority | Alarm priority level | No |
| Message | Text displayed when alarm triggers | No |
| Disable | Enable/disable the alarm | No |
| Deadband | Range where changes are ignored | No |
| Setpoint | Target value for deviation alarms | No |
| SetpointDeadband | Range around setpoint to ignore | No |
| AuxValue | Additional information field | No |
| AuxValue2 | Secondary auxiliary value | No |
| AuxValue3 | Tertiary auxiliary value | No |
| Comment | Notes about the alarm item | No |
Alarm Conditions
| Condition | Description | Formula |
|---|---|---|
| Hi | High alarm | Tag ≥ Limit |
| HiHi | High-high alarm (auto-acks Hi) | Tag ≥ Limit |
| Lo | Low alarm | Tag ≤ Limit |
| LoLo | Low-low alarm (auto-acks Lo) | Tag ≤ Limit |
| RateOfChange | Rate exceeds limit | ΔTag/Δt ≥ Limit (s) |
| DeviationMinor | Minor deviation from setpoint | |Tag - Setpoint| > Limit |
| DeviationMajor | Major deviation from setpoint | |Tag - Setpoint| > Limit |
| Equal | Exact match | Tag = Limit |
| GreaterThan | Greater than | Tag > Limit |
| GreaterEqual | Greater or equal | Tag ≥ Limit |
| LessThan | Less than | Tag < Limit |
| LessEqual | Less or equal | Tag ≤ Limit |
| Changed | Any change | Tag value changed |
| ChangedUp | Value increased | Tag value increased |
| ChangedDown | Value decreased | Tag value decreased |
| NotEqual | Not equal | Tag ≠ Limit |
Alarms will be generated even when the quality differs from 192 (good).
Creating Alarm Items
- Navigate to Alarms → Items
- Enter TagName or select from tag list
- Select Condition type
- Set Limit threshold value
- Choose AlarmGroup for behavior
- Press Enter to save
Example configuration:
TagName: Tank1.Temperature
Condition: HiHi
Limit: 95
Group: Critical
Message: "Tank 1 Critical Temperature"
Priority: 100Shift-Based Limits
Use multiple limit values for different operational periods:
| Property | Usage |
|---|---|
| Limit | Default/primary threshold |
| Limit1 | Secondary threshold (e.g., day shift) |
| Limit2 | Tertiary threshold (e.g., night shift) |
Enable via Alarms → Global Settings → Enable LimitsByShift
Deadband Configuration
Prevents alarm chattering:
Value Deadband:
- Alarm triggers at Limit
- Must drop below (Limit - Deadband) to clear
- Must exceed (Limit + Deadband) to re-trigger
Setpoint Deadband:
- Applied around setpoint for deviation alarms
- Prevents minor fluctuations from triggering
Runtime Properties
Access alarm item state at runtime via @Alarm.Item.[ItemName]:
// Check alarm state bool active = @Alarm.Item.HighTemp.Alarm == 1; DateTime activeTime = @Alarm.Item.HighTemp.ActiveTime; // Get current values string currentValue = @Alarm.Item.HighTemp.LastValue; double limitValue = @Alarm.Item.HighTemp.Limit;
Best Practices Checklist
- Use meaningful names - TagName should clearly identify the monitored point
- Set appropriate deadbands - Prevent alarm flooding from oscillating values
- Configure priority levels - Critical alarms get higher priority
- Write descriptive messages - Include context and severity in alarm text
- Group related alarms - Use AlarmGroups for common behaviors
- Document with comments - Use Comment field for maintenance notes
- Test conditions - Verify alarms trigger at expected values
Troubleshooting
Alarm not triggering:
- Verify TagName is valid
- Check Condition logic matches requirement
- Ensure not Disabled
- Confirm AlarmGroup is active
Excessive alarms:
- Increase Deadband value
- Review trigger Condition
- Check for tag oscillation
- Consider time deadband in AlarmGroup
Wrong threshold:
- Verify Limit value
- Check shift-based limits if enabled
- Confirm Setpoint for deviation alarms