Alarm Groups (Reference) define shared characteristics and behaviors for collections of related alarm items in your FrameworX solution. Alarm Groups enable:
- Collective configuration of alarm behaviors
- Shared acknowledgment requirements
- Common notification methods
- Unified visual and audio alerts
- Centralized logging preferences
- Consistent timeout settings
The platform provides pre-defined groups (Critical, Warning, AuditTrail) for common use cases, plus support for custom groups.
Configuration Properties
| Property | Description | Required |
|---|---|---|
| Name | Group identifier | Yes |
| AckRequired | Requires operator acknowledgment | Yes |
| ActiveTimeDeadband | Time period to ignore active alarms | No |
| AckTimeout | Timeout period for acknowledgment | No |
| AutoAckTime | Auto-acknowledge after this time | No |
| Sound | Audio file for alarm notification | No |
| Show | Display alarms from this group | Yes |
| LogEvents | Log events to historian | Yes |
| Colors | Visual identification colors | No |
| NotificationMethod | Script method for notifications. From FrameworX 10.1.6, also a webhook or MQTT broker URI (http://, https://, mqtt://, mqtts://). See Alarms Notifications Reference. | No |
| Category | Category designation | No |
| Description | Group purpose and details | No |
Pre-Defined Groups
| Group | Purpose | Default Settings |
|---|---|---|
| Critical | High-priority alarms requiring immediate action | AckRequired=True, LogEvents=True, High Priority |
| Warning | Medium/low-priority informational alarms | AckRequired=False, LogEvents=True, Medium Priority |
| AuditTrail | Hidden alarms for audit logging only | Show=False, LogEvents=True, No Display |
Creating Alarm Groups
- Navigate to Alarms → Groups
- Click Plus icon
- Enter Name and Description
- Click OK
- Edit properties by double-clicking
- Press Enter to save changes
Before deleting: Ensure no AlarmItems are linked to the group. Check via Alarms → Items and use Track Changes → Cross Reference.
Acknowledgment Settings
| Property | Behavior |
|---|---|
| AckRequired | Alarm stays active until acknowledged, even if condition clears |
| AckTimeout | Maximum time allowed for acknowledgment |
| AutoAckTime | Automatically acknowledge after specified time |
Example flow:
Alarm Triggered → Wait for Ack → AutoAckTime expires → Auto-acknowledged
↓
Manual Ack → AcknowledgedNotification Configuration
Sound Alerts
- Configure via Sound property
- Plays continuously until acknowledged
- Different sounds for different severities
- See [Alarm Groups Sounds] for audio file setup
Visual Indicators
- Colors property defines alarm states
- Applied in alarm displays
- Consistent across all items in group
Custom Notifications
NotificationMethod calls Script Class methods:
// In Script Class
public void SendCriticalAlert(AlarmEventArgs args)
{
// Send email
EmailService.Send(args.Message, args.Priority);
// Send SMS
SMSService.Alert(args.TagName, args.Value);
// Log to external system
ExternalLogger.LogAlarm(args);
}Configure: NotificationMethod = "Script.Class.ServerMain.SendCriticalAlert"
Webhook and MQTT Notifications
From FrameworX 10.1.6, NotificationMethod also accepts a webhook or MQTT broker URI, for example https://alerts.example.com/fx/alarms or mqtts://broker.example.com/plant1/alarms. The runtime then sends the alarm events of the group to the target with no script, and keeps them in a store-and-forward buffer while the target is unreachable. For the URI formats, the message content and the delivery rules, see Alarms Notifications Reference.
Deadband and Timing
ActiveTimeDeadband
Prevents alarm flooding during startup or known conditions:
- Ignores alarms for specified seconds
- Useful during system initialization
- Prevents nuisance alarms
Time-Based Acknowledgment
AckTimeout = 300 // Must acknowledge within 5 minutes
AutoAckTime = 600 // Auto-acknowledge after 10 minutes if not handledRuntime Access
Access group properties at runtime:
// Check if acknowledgment required
bool needsAck = @Alarm.Group.Critical.AckRequired;
// Get active alarm count for group
int criticalCount = @Alarm.Group.Critical.TotalCount;
// Disable group (set Disable to 0 to re-enable)
@Alarm.Group.Warning.Disable = 1;Acknowledge All Alarms in a Group
AckAll on a group is a change-triggered command property, not a method. Each change of value acknowledges every unacknowledged alarm item in the group. Writing the same value again does nothing, so a button that always writes 1 acknowledges only the first time. To acknowledge again, change the value once: use the Toggle action (ActionType ToggleValue), or write the current value + 1. Setting the value to 0 and back to 1 in the same script does not reliably acknowledge. This behavior applies to FrameworX 10.1.5 and 10.1.6.
// Acknowledge every unacknowledged alarm in the Critical group
@Alarm.Group.Critical.AckAll = @Alarm.Group.Critical.AckAll + 1;Common Configurations
Critical Process Alarms
Name: ProcessCritical
AckRequired: True
Sound: Critical.wav
LogEvents: True
AutoAckTime: 0 (never)
Colors: Red
NotificationMethod: Script.Class.Notifications.SendCriticalInformational Logging
Name: InfoLog
AckRequired: False
Show: False
LogEvents: True
Category: AuditMaintenance Alarms
Name: Maintenance
AckRequired: True
AutoAckTime: 3600 (1 hour)
LogEvents: True
NotificationMethod: Script.Class.Maintenance.ScheduleWorkBest Practices Checklist
- Group by severity - Critical, Warning, Information
- Consistent sounds - Same severity = same sound
- Clear naming - Group name indicates purpose
- Document settings - Use Description field
- Test notifications - Verify all alert methods work
- Set appropriate timeouts - Balance responsiveness vs alarm fatigue
- Use categories - Organize groups logically
Troubleshooting
Alarms not showing:
- Check Show property is True
- Verify display filter includes group
- Confirm AlarmItems assigned to group
No sound playing:
- Verify sound file path correct
- Check audio system enabled
- Confirm AckRequired if sound should repeat
Notifications not sent:
- Verify NotificationMethod syntax
- Check Script Class method exists
- Review method error logs
- For a webhook or MQTT target (from FrameworX 10.1.6), read
Alarm.LastErrorMessage. It says when events were buffered and why.
Auto-acknowledge not working:
- Confirm AutoAckTime > 0
- Check AckRequired is True
- Verify no manual ack occurred